GETTING STARTED
Caution Caution: The meter has no power-on switch, so it will be in operation as soon as you apply power.

If you power off/on the meter, or perform a hard reset (press the RESET button twice), the meter shows "RST" followed by "STRN".

RATING/PRODUCT LABEL
This label is located on top of the meter housing.

CHECKING OR CHANGING MAIN BOARD POWER JUMPERS (Factory Set)
Caution Important: If you want to change the factory preset jumpers, do the following steps, otherwise go to Section 3.3.

Disconnect the power from the unit before proceeding.

1. Remove the main board from the case. Refer to Section 2.6.

2.
Locate the solder jumpers W1, W2, and W3 (located near the edge of the main board alongside the transformer).

3.
If your power requirement is 115 V ac, solder jumpers W1 and W3 should be wired, but jumper W2 should not. If your power requirement is 230 V ac, solder jumper W2 should be wired, but jumpers W1 and W3 should not.
NOTE: W4 jumper is not used.

Figure 3-1 shows the location of solder jumpers W1 through W3.
Power Jumper Detail
Figure 3-1. Power Jumper Detail (W1 - W3)

Figure 3-2 shows the location of jumper positions on the main board.
Main Board Jumper Positions
Main Board Jumper Positions
Figure 3-2. Main Board Jumper Positions

S2 jumpers are for testing purposes. Do not use as reading errors may result.

S3 jumpers are used for the following (refer to Table 3-2):
* To enable or disable the front panel push-buttons
* To allow for an extremely low resistance load for analog output
* To disable the MENU button
* To perform calibration procedure

Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may result.


S3 Jumper Functions Table 6-1
JUMPER
DESCRIPTION
S3-A
Default: Installed. Remove to disable all front panel push-buttons Installed. Remove to disable all front panel push-buttons
S3-B
Default: Removed. Install for meter calibration.
S3-C
Default: Removed. Install for analog output when load is less than 1 KW impedance. Care should be taken when installing this jumper.
S3-D
Default: Installed.
S3-E
Default: Removed. If installed without S3-B, MENU locks out. (Pressing the MENU button while in the RUN mode results in the display showing LOCK and returns to the run mode).

PANEL MOUNTING
1. Cut a hole in your panel, as shown in Figure 3-4.

2.
Insert the meter into the hole. Be sure the front bezel is flush to the panel when tightening mounting brackets..

3. Proceed to Section 3.4 to connect your sensor input and main power.
Meter-Exploded View
Figure 3-3. Meter - Exploded View
Panel Cut-Out

Figure 3-5
Panel Cut-Out

CONNECTING SENSOR INPUT
Figures 3-5 shows excitation supplied from the meterÆs internal supply (50mA maximum). Select 5, 10, or 12 volt excitation at DIP switch.

Meter-powered Bridge Input
Figure 3-5
Meter-powered Bridge Input
Externally-powered Bridge Input
Figure 3-6
Externally-powered Bridge Input

Figure 3-6 shows the connections required for an externally-powered bridge input: the external supply is brought to the meter's buffer circuits to permit ratiometric readings. Set S1 DIP switch for external excitation for Figures 3-6 and 3-7.

4-Wire Voltage Input w/external excitation

Figure 3-7
4-Wire Voltage Input Connections with External Excitation
4-Wire Voltage Input w/internal excitation

Figure 3-8
Current Input Connections with Internal Excitation
Current Input Connections w/External Excitation
Figure 3-12. Current Input Connections with External Excitation

CONNECTING MAIN POWER
Connect the ac main power connections as shown in Figure 3-10.
WARNING:
Do not connect AC power to your meter until you have completed all input and output connections. Failure to do so may result in injury!

Connect the DC main power as shown in Figure 3-13.

Main Power Connections - AC
Figure 3-10. Main Power Connections - AC

Table 3-1 shows the wire color and respective terminal connections for both USA and Europe.
AC Power Connections Table 3-2
AC POWER
WIRE COLORS
EUROPE
USA
AC Line
Brown
Black
AC Neutral
Blue
White
AC Earth Ground
Green/Yellow
Green

Connect the AC main power connections as shown in Figure 3-11.
Main Power Connections - DC
Figure 3-11
Main Power Connections - DC
Analog Output Connections

Figure 3-12
Analog Output Connections

CONNECTING ANALOG AND RELAY OUTPUT
If you have purchased a meter with analog or dual relay output, refer to the following drawings for output connections.

Relay Output Connections

Figure 3-13. Relay Output Connections
Help Price List Specifications Print Manual Manuals Home
 Home Home  Table of Contents TOC Back  Back  Next Next